Download PDF version. Transportation data sheet PDF also available!

E.S.P. SRL logo
TECHNICAL SHEET STATIONARY (ELECTRICAL)


PRODUCT DESCRIPTION AND DATA SHEET

ESP Fire Stryker is an automatic, fixed aerosol inhibitor with remarkable extinguishing capability. It has very low toxicity and is environmentally safe. The extinguishing compound is encapsulated in a stainless steel casing of various sizes, according to each model of ESP Fire Stryker (see specifications section). The external metallic casing is equipped with mounting brackets suitable to be wall or floor mounted and with two electrical cables to serve as connections for the electric igniter to the remote temperature/smoke sensors (both to be activated either in the automatic or manual modes).

The use of a potassium powder jet – a unique method among fire extinguishers – involves the vaporization of the powder in the environment followed by the condensation of its extinguishing substance. The product works by interrupting a fire’s chain of reaction (the “auto-catalyst” of the fire). The device is composed of stable, solid minerals; it does not contain gas and is not pressurized. The aerosol-like jet is only produced when the charger is stricken with its base. The produced aerosol jet is essentially an inert salt that emits gas already present in the atmosphere.

This process allows ESP Fire Stryker to extinguish all types of fires through saturation. Its slow bio-degradation in the environment furthers the prevention of subsequent fires.

The extinguishing process involves two different reactions: one is physical and the other, chemical. The physical reaction relates to potassium’s tendency to oxidize rapidly in air. When in contact with air, alkaline salts consume great quantities of oxygen, thus depriving fires of oxygen. The chemical reaction is created through the stable link between potassium particles and the fire’s combustion particles.

Through the two reactions, a quick oxidation process takes place, immediately transforming the jet from a solid state into a gaseous state which frees the potassium particles. These atoms are able to intercept and interrupt any other free particles produced by the fire’s chain reaction combustion process. Potassium has strong inhibitor qualities, due to its weak ionization energies.



FEATURES

ESP Fire Stryker potential impact on the environment and on users:

• ODP Ozone Depletion Potential = zero • GWP Global Warming Potential = zero
• ATL Atmospheric Life Time = zero • Electric conductibility: none
• Activation time: Immediate • Electrostatic discharge: none
• Usability temperature: from -140º F to +320º F • Usability humidity: up to 98% U.R.
• Granulometry: from 2 to 4 microns • Corrosiveness: none
• Steam: none • Thermal shock: none
• Residue after use: negligible • Not dangerous to human health
• Does not produce any “organic accumulation” • Very low toxicity
• Environmentally safe • Unlimited shelf life
• The device is not pressurized • The device does not need to be tested
• The device is not considered hazardous material • The device does not need maintenance




APPLICATIONS

Due to its fast activation and response time, ESP Fire Stryker is suitable for use in indoor applications such as:
  • WORKSHOPS • TELECOMMUNICATION AND PROCESS CONTROL ROOMS
  • GENERAL INDUSTRIAL HAZARDS • DATA PROCESSING FACILITIES
  • SMALL BOATS • GENERATOR ENCLOSURES

ESP FIRE STRYKER is capable of extinguishing fires in different classes:
• Class A: Solid material, ordinary combustibles, such as wood, paper, fabric, plastics, etc.
• Class B: Flammable liquids, such as gasoline, oil based paints, solvents, alcohol, acetone, etc.
• Class C: Gaseous category: GLP, methane, acetylene, etc.
• Class E: electrical equipment fires subject to voltages up to 100.000v at a distance of 1m; Cable galleries, distribution cabinets, electronic devices



ESP SRL (MANUFACTURER) EXISTING CERTIFICATIONS

ISO 9001:2008 (Standards for quality management systems)
Declaration of CE Conformity
(Certifies that product has met EU consumer safety, health or environmental requirements.)

PRODUCT CERTIFICATION AND TEST REPORTS:

For complete list, please see Certifications.



SPECIFICATIONS

PARAMETER
100G1E
200G2E
500G5E
1000G10E
2000G20E
3500G35E
5000G50E
Extinguishing Mass (Kg.)
0.10
0.20
0.50
1.00
2.00
3.50
5.00
Weight (Kg.)
0.25
0.35
3.5
6
14
21
30
Width (mm.)
-
-
70
70
120
140
200
Length (mm.)
205
250
220
320
350
400
440
Height (mm.)
-
-
200
250
300
340
400
Diameter (mm.)
35
35
-
-
-
-
-
Discharge Time (Sec.)
50
90
60
90
100
105
130
Minimum ignition current in mA
370
370
370
370
370
370
370
Suggested ignition in A
> 0,9
> 0,9
> 0,9
> 0,9
> 0,9
> 0,9
> 0,9
Minimum current time to ignite
2 ms at
1,0 A
2 ms at
1,0 A
2 ms at
1,0 A
2 ms at
1,0 A
2 ms at
1,0 A
2 ms at
1,0 A
2 ms at
1,0 A


COVERAGE PARAMETERS


PART NUMBER
MODEL
MAX VOLUME COVERAGE CUBIC METERS
100G1E
100E
1.5
200G2E
200E
3
500G5E
500E
7.5
1000G10E
1000E
15
2000G20E
2000E
30
3500G35E
3500E
52.5
5000G50E
5000E
75


HANDLING / STORAGE PARAMETERS

Normal attention in handling.
In case of unintentional activation of the flame inhibitor, wait for the complete aerosol discharge and ventilate the area.
Avoid the direct contact of the product with open flames.
Store at a temperature between -10°C and +50°C (+14°F and + 122°F).
Packaging in cardboard boxes; do not pile the boxes higher than 2 meters



TRANSPORTATION CLASSIFICATION CODES

Transport by railway (RID/ADR) ADR 4.1
Transport by sea (MDD rule) 4.1
Transport by plane (ICAO-IATA rule) Class 5.1, Packing Group III
UN Identification Code number UN 3178



DISCLAIMER

The information contained in this sheet is intended to be of a general use only. The manufacturer may at any time and from time to time, for technical or other necessary reasons, modify any of the details or specifications of the product(s) described in this brochure. Illustrations do no necessarily show products in standard condition. The dimensions, weights and capacities shown herein, as well as any conversion data used, are approximate only and are subject to variations within normal manufacturing techniques. To be sure of getting accurate, detailed, and up-to-date information, any intending buyer should consult his nearest distributor, dealer or representative.


 

Video Demo About Home CertificationsTestimonialsTech Specs Distributors